ETHOS floor-standing boiler

Designed and manufactured in the UK, the ETHOS stainless steel “twin burner” boilers have been developed to meet the requirements of today’s commercial buildings.

Key features:

  • Available in 350 and 550kW models – Installation options allowing 17.5kW > 3.3mW
  • 2 premix burners per boiler – Nox levels of 31mg/kW
  • Stainless steel heat exchanger – 5-year heat exchanger warranty
ukca_+_ce
product_warranty_2_year

Specification

General
Dimensions (Height x Width x Depth)1300 mm x 750 mm x 1100 mm
Water Content of Appliance25 litres
Weight - empty234-370 kg
Connections
Connections - flow/returnDN50/65 PN16 Flange
Connection - gas1½ " BSP
Connection - flue150-180 mm
Electrical
Power supply (Vac/Ph/Hz)230 V a.c. / 1 / 50 Hz
Power consumption558-898 W
Fuse protection10 amp
Maximum Fan Speed6100-9200 RPM
Minimum Fan Speed1300-1950 RPM
Heating Performance
Nominal heat input (nett)17.5-350.0 kW - 27.5-550.0 kW
Nominal heat output at 80/60°C17.2-343.0 kW - 27.0-539.0 kW
Nominal heat output at 50/30°C18.9-378.0 kW 39.7-594.0 kW
Maximum gas consumption (G20)35.5-56.1 m³/hr
Maximum gas consumption (G25)40.4-62.1 m³/hr
Maximum gas consumption (G31)13.6-20.9 m³/hr
Technical Data
Flue gas dew point52°C
Flue temperature at 80/60°C (at ambient temperature of 20°C)75°C
Flue material temperature classT 120
Permitted maximum resistance of the flue system200-250 Pa
Condensation pH value3.0 - 5.5
Maximum CH flow temperature90°C
CH water pressure (min - max)0.5 - 6.0 bar
Minimum/maximum gas pressure (G20)17 - 20 mbar
Minimum/maximum gas pressure (G25)17 - 20 mbar
Minimum/maximum gas pressure (G31)30 - 50 mbar
Environmental Data
NOx levels31.0 mg/kW
Maximum efficiency (nett non condensing)98.1-98.3 %
Maximum efficiency (nett condensing)108.9 %
Seasonal efficiency95.6 %

Model Options

ModelPart no.
ETHOS 350FSB320350
ETHOS 550FSB320550
ETHOS RS 350FSB330350
ETHOS RS 550FSB330550

More Features

With an unsurpassed premix burner modulation of 20 > 1 and output capability from 17.5kW > 3.3mW, the ETHOS FS range ensures your building load is accurately matched, whatever the season.

As with the wall-mounted boilers the FS range also has onboard boiler cascade control.

Resources

Can't find what you are looking for?

Call now