Specification
| RA-ASHP-R290-040 | RA-ASHP-R290-050 | |
| Energy Rating | A+++/A++ | A+++/A++ |
| Cooling | ||
| Cooling capacity 1 (kW) | 28.9 | 34.1 |
| Power input 1 (kW) | 9.2 | 11 |
| E.E.R. 1 (W/W) | 3.14 | 3.1 |
| Cooling capacity 2 (kW) | 34.5 | 37 |
| Power input 2 (kW) | 8.1 | 8.53 |
| E.E.R. 2 (W/W) | 4.26 | 4.34 |
| SEER 5 (W/W) | 4.86 | 4.8 |
| Water flow rate 1 (l/s) | 1.38 | 1.63 |
| Pressure drop on hydronic circuit side 1 (kPa) | 24 | 26 |
| Heating | ||
| SCOP 6 (W/W) | 4.09 | 4.2 |
| Heating capacity 3 (kW) | 40.1 | 50 |
| Power input 3 (kW) | 9.8 | 11.9 |
| COP 3 (W/W) | 4.1 | 4.2 |
| Heating capacity 4 (kW) | 38 | 47.9 |
| Power input 4 (kW) | 13.1 | 16.5 |
| COP 4 (W/W) | 2.9 | 2.9 |
| Heating capacity 12 (kW) | 38.4 | 45.8 |
| Power input 12 (kW) | 16 | 18.8 |
| COP 12 (W/W) | 2.4 | 2.44 |
| Water flow rate 4 (l/s) | 1.14 | 1.43 |
| Pressure drop on hydronic circuit side 4 (kPa) | 20 | 26 |
| Noise Level | ||
| Sound power Lw 9 (dB (A)) | 82 | 83 |
| Power | ||
| Power supply | 400V/3P+N+T/50Hz | 400V/3P+N+T/50Hz |
| Phase | 3 Phase | 3 Phase |
| Refrigerant | R290 | R290 |
| Dimensions | ||
| Length (mm) | 1850 | 1850 |
| Length with tank (mm) | 2460 | 2460 |
| Depth (mm) | 1110 | 1110 |
| Height (mm) | 1980 | 1980 |
- Cooling: outdoor air temperature 35°C; in/out water temperature 12/7°C.
- Cooling: outdoor air temperature 35°C; in/out water temperature 23/18°C.
- Heating: outdoor air temperature 7°C db 6°C wb; in/out water temperature 30/35°C.
- Heating: outdoor air temperature 7°C db 6°C wb; in/out water temperature 47/55°C.
- Cooling: low temperature, variable output, fixed flow rate.
- Heating: average climatic conditions; Tbiv=-7°C; low temperature, variable output, fixed flow rate.
- Indicative data subject to changes. For the correct value, always refer to the technical label on the unit.
- Calculated for a decrease in system water temperature of 10°C with a defrost cycle lasting 6 minutes.
- Sound power: heating mode according to EN 12102:2022; value determined on the basis of measurements made in accordance with UNI EN ISO 9614-1, in compliance with Eurovent certification requirements.
- Sound pressure: value calculated from the sound power level using the standard ISO 3744:2010 at a distance of 1 m.
- Heating: outdoor air temperature 7°C db 6°C wb; in/out water temperature 55/65°C.
Model Options
| Model | |
|---|---|
| RA-ASHP-R290-040 | 40 kW |
| RA-ASHP-R290-050 | 50 kW |
More Features
- Single solution for heating and hot water production
- Unique design integrates advanced technical solutions and modern aesthetics
- Designed to generate high water temperature even in the harshest conditions
- Modbus connectivity
- User-friendly touchscreen control system
- Anti-freeze and anti-vibration technology
- Can be configured in a cascade of up to 7 units
Accessories supplied separately
- Deaerator
- Hot water remote probe
- Anti-vibration kit
- Touchscreen display options for single unit and cascade
Controls
Inverter heat pump with BMS, integral controls, safety lockout, and frost/weather support.
Hydraulics
Standard connections and integral relief valves for heating and indirect DHW.
Dimensions
Standard chassis for uniform cascades.
Product warranty
Available with a 2-year warranty if commissioned by an approved partner, 1-year as standard.
Hydraulic performance
The maximum operating pressure is 6 bar, and it is suitable for heating and indirect hot water systems.
Efficiency
R290 (GWP 3), A++ energy rating.
Product approvals
Eurovent certified performance.